UPS Battery Cabinet and Battery Module
Power-Critical Facilities Recovery Solutions
Application
PTE provides modular UPS battery and battery cabinets for semiconductor facilities, industrial plants, warehouses, healthcare environments, and other critical infrastructure. Designed for high availability environments where power quality, voltage stability, and serviceability matter as much as backup runtime, our systems help support stable operation during power disturbances, voltage events, and unexpected outages. Integrated HMI touchscreen monitoring provides real-time system visibility, while standardized modular design simplifies maintenance and field service.
Products
2450/24100 Modular Battery Module
- Standardized module design
- Integrated BMU (Battery Management Unit) for voltage and temperature sensing
- Front-access BMU replacement for easier field service
- Front terminal design with busbar or power-cable connection options
- Nine integrated temperature sensors per battery module
- Designed for medium- to high-rate discharge performance
![]() |
![]() |
請左右滑動表格
| Item | 2450 Standard Battery Pack | 24100 Standard Battery Pack |
|---|---|---|
| Nominal Voltage | 25.6V | 25.6V |
| Rated Capacity | 50Ah | 100Ah |
| Rated Energy | 1.28kWh | 2.56kWh |
| Max. Charging Current | 50A | 100A |
| Max. Discharging Current | 350A (7C) | 400A (4C) |
| Dimension W*D*H | 130*635*228mm | 130*635*247.6mm |
| Weight | 16.6 ± 0.5kg | 29 ± 0.5kg |
| Operating Temperature | Charger 0 ~ 35 ℃ Discharge -10 ~ 35 ℃ |
Charger 0 ~ 35 ℃ Discharge -10 ~ 35 ℃ |
| Certifications | UN 38.3 / UL 1973 / UL 9540A | UN 38.3 / UL 1973 / UL 9540A |
|
UPS Battery Cabinet
|
![]() |
請左右滑動表格
| Item | 2450 Battery Cabinet | 24100 Battery Cabinet |
|---|---|---|
| Nominal Voltage | 512V | 512V |
| Rated Capacity | 50Ah | 100Ah |
| Rated Energy | 25.6kWh | 51.2kWh |
| Max. Charging Current | 50A | 100A |
| Max. Discharge Current | 350A (7C) | 400A (4C) |
| Dimension W*D*H | 600*800*2,000mm | 600*800*2,100mm |
| Weight | 550 ± 10kg | 750 ± 10kg |
| Operating temperature | Charge 0 ~ 35 ℃ Discharge -10 ~ 35 ℃ |
Charge 0 ~ 35 ℃ Discharge -10 ~ 35 ℃ |